C27 (60Hz)

Cat C27 (60 Hz)

Scroll for more info about

Specifications

Generator Set Specifications
Height - Maximum 85.1 in
Length - Maximum 184
Width - Maximum 67.8 in
Minimum Rating 680 ekW
Maximum Rating 800 ekW
Voltage 208 to 600
Frequency 60 Hz
Speed 1800 RPM
Generator Set Configurations
Emissions/Fuel Strategy Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards)
Engine Specifications
Engine Model C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
Compression Ratio 16.5:1
Aspiration TA
Governor Type Adem™A4
Fuel System MEUI
Bore 5.4 in
Displacement 1649.47 in³
Stroke 6 in

Features

Design Criteria

Design Criteria
The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.

Cat Diesel Engine

Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • Generator

    Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • Cat EMCP Control Panel

    Cat EMCP Control Panel
    The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

    Single-Source Supplier

    Single-Source Supplier
    Fully prototype tested with certified torsional vibration analysis available

    World Wide Product Support

    World Wide Product Support
    Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

    Seismic Certification

    Seismic Certification
  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
  • UL 2200 / CSA - Optional

    UL 2200 / CSA - Optional
  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.
  • 360� Exterior View (HTML)

    360� Exterior view. Double click on the image to zoom in on any area of the product.