Cat C15 (50 Hz)

Generator sets

  • Rating: 365 - 550 kVA
  • EU Emission certified (EU Stage IIIA)
C837819.png

About the Cat C15 (50 Hz)

 

The C15 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 365 to 550 kVA at 50 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 percent rated load in one step. The engines are certified to the US EPA Tier 4 Final emissions levels. Seismic certification is also available for select models, so you can deliver power despite disturbances. Our integrated control system, including ATS and switchgear ensure a consistent power supply and connection to your fleet through on-site and remote monitoring options. We offer a wide range of EMCP 4 control panel options, with a simple screen display, consolidating all your management and diagnostics tools. The optional EMCP 4.4 provides multi generator set paralleling capability, allowing you to use multiple generator sets for increased power output and improved reliability. It's not just quality that matters but customization, choose from a broad range of accessories and bolt-on system expansion attachments. Discover our flexible upgradeable packaging options to work with your spatial restrictions and environmental conditions. Our C15 generator sets are developed for such prerequisites, so that you can meet your specific power needs.

Specifications

Generator Set Specifications
Height - Maximum 86.3 in
Length - Maximum 150.8 in
Width - Maximum 58.3 in
Minimum Rating 365 kVA
Maximum Rating 550 kVA
Voltage 208 to 600 Volts
Frequency 50 Hz
Speed 1500 RPM
Generator Set Configurations
Emissions/Fuel Strategy Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 or Tier 3 Nonroad Equivalent Emission Standards), EU Stage IIIA Nonroad Emission Standards, China Nonroad III Emission Standards
Engine Specifications
Engine Model C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Governor Type Adem™A4
Fuel System MEUI
Bore 5.4 in
Displacement 927.56 in³
Stroke 6.75 in

Features

Cat Diesel Engine

Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • Generator

    Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • Cat EMCP Control Panel

    Cat EMCP Control Panel
    The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

    Seismic Certification

    Seismic Certification
  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
  • Single-Source Supplier

    Single-Source Supplier
    Fully prototype tested with certified torsional vibration analysis available

    World Wide Product Support

    World Wide Product Support
    Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

    Design Criteria

    Design Criteria
    The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.

    Contact us

     

    Do you have questions or need advice? We are happy to help.

     

    • Call
    • Arrow

    Request a quotation

     

    Country *
    Banner - Contact Sticky Desktop Banner - Contact Sticky Mobile
    • Call
    • Arrow

    Call us

    Available during office hours from 08.00 - 18.00.

     

    Email us

    We will get in contact within 24 hours.

    How would you like to be contacted by us? *
    What are you looking for? *
    250/250

    Please fill the form below and I will contact you as soon as possible.

    How would you like us to contact you? *
    250/250
    web-monitoring-ok