Cat 3516C Tier 4 Final (60 Hz)

Scroll for more info about

Specifications

Generator Set Specifications
Height - Maximum 118.5 in
Length - Maximum 277 in
Width - Maximum 101.2 in
Minimum Rating 1650 ekW
Maximum Rating 2500 ekW
Voltage 480 to 13800 volts
Frequency 60 Hz
Speed 1800 RPM
Generator Set Configurations
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset
Engine Specifications
Engine Model 3516C HD, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Compression Ratio 14.7:1
Aspiration TA
Governor Type ADEM™A4
Fuel System Electronic unit injection
Bore 6.69 in
Displacement - HD 4764.73 in³
Stroke - HD 8.46 in

Features

Cat Generator Set Package

Cat Generator Set Package
Cat generator set packages have been fully prototype tested, and certified torsional vibration analysis reports are available. The packages are designed to accept 100% load in one step, meet the NFPA 110 requirement for loading, and conform to the ISO 8528-5 steady state and transient response requirements.

Cat Diesel Tier 4 Final Certified Engines

Cat Diesel Tier 4 Final Certified Engines
The four cycle Cat diesel engine combines consistent performance with excellent fuel economy and transient response that meets or exceeds ISO 8528-5. The engines have been designed and built for a wide range of applications are certified to the US EPA Tier 4 Final emissions requirements. The engines feature a reliable, rugged, and durable design that has been field proven in thousands of applications worldwide from emergency standby installations to continuously operating power plants.

Cat Clean Emissions Module (CEM)

Cat Clean Emissions Module (CEM)
The Tier 4 Final engine has been optimized to work with the Cat CEM. The CEM is a reliable, compact, and lightweight system that gives maximum installation flexibility. It features a diesel oxidation catalyst for particulate matter (PM) and hydrocarbon (HC) control. Selective catalytic reduction (SCR) reduces NOx output and provides integrated sound attenuation. The CEM is controlled by a separate dosing module that has been integrated into the standard generator set controls for complete monitoring, protection and closed loop NOx control. For more information on the CEM, refer to cut sheet LEHE0359.

Generators

Generators
The generators used on Cat packages have been designed and tested to work with the Cat engine. The generators are built with robust Class H insulation and provide industry leading motor starting capability. Random wound generators provide good generator performance in a majority of applications and form wound is available for harsh mechanical and electrical environments.

EMCP Control Panels

EMCP Control Panels
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules.

Cooling System

Cooling System
The cooling system has been designed to operate in standard ambient temperatures up to 50°C (122°F), with optional high ambient radiators available. The factory installed cooling system has been designed and tested to ensure proper generator set cooling, and includes the radiator, fan, belts, and all guarding installed as standard. Contact your Cat Dealer for specific ambient and altitude capabilities

Seismic Certification

Seismic Certification
The complete generator set package has been certified to meet the requirements of the IBC and OSHPD requirements. Certification consisted of both mathematical analysis and full shake table testing of the generator set in a simulated earthquake condition.

World Wide Product Support

World Wide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.

Contact

 

Contact us for any advise.

More about tailor made solutions?

 

  • Call
  • Arrow

The brochure is ready.

Just fill in your email adress and we'll send you the brochure immediately.

 

  • Call
  • Arrow

Email us

 

We will make contact within 24 hours.

 

How would you like us to contact you?
Department

Shopping cart