Cat C18 (50 Hz)

Dieselgeneratorer

Om Cat C18 (50 Hz)

 

The C18 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 550 to 715 kVA at 50 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 percent rated load in one step. Our C18 generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certified. Seismic certification is also available for select models, so you can deliver power despite disturbances. Our integrated control system, including ATS and switchgear ensure a consistent power supply and connection to your fleet through on-site and remote monitoring options. We offer a wide range of EMCP 4 control panel options, with a simple screen display, consolidating all your management and diagnostics tools. The optional EMCP 4.4 provides multi generator set paralleling capability, allowing you to use multiple generator sets for increased power output and improved reliability. It's not just quality that matters but customization, choose from a broad range of accessories and bolt-on system expansion attachments. Discover our upgradeable packaging options to work with your spatial restrictions and environmental conditions. Our C18 generator sets are developed for such prerequisites, so that you can meet your specific power needs.

Spesifikasjoner

Generator Set Specifications
Maximum Rating 715 kVA
Minimum Rating 550 kVA
Emissions/Fuel Strategy Low Fuel, China Nonroad III Emis Stds
Voltage 380 to 415 Volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Prime
Engine Specifications
Motormodel C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 145 mm
Stroke 183 mm
Displacement 18.13 l
Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Fuel System Electronic unit injection
Governor Type Ademâ„¢A4
Generator Set Dimensions
Length - Maximum 4135 mm
Width - Maximum 1989 mm
Height - Maximum 1906 mm
Generator Set Specifications
Maximum Rating 850 kVA
Minimum Rating 706 kVA
Emissions/Fuel Strategy Low Fuel
Voltage 380 to 415 Volts
Frequency 50 Hz
Speed 1500
Duty Cycle Standby, Prime
Engine Specifications
Motormodel C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 145 mm
Stroke 183 mm
Displacement 18.1 l
Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Fuel System Electronic unit injection
Governor Type Adem™A4
Generator Set Dimensions
Length - Maximum 4135 mm
Width - Maximum 1989 mm
Height - Maximum 1906 mm

Egenskaper

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Generator Set Package

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Cat Diesel Engine

A-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
M-Frame Alternator

GCCP1.3 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
GCCP 1.3 Control Panel

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Cooling System

Certifications

Certifications

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
One Safe Source

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
World Wide Product Support

Design Criteria

The generator set meets NFPA 110 loading requirement and meets ISO 8528-5 transient response.
Design Criteria

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Cat Diesel Engine

A-Frame Alternator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
M-Frame Alternator

GCCP 1.3 Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
GCCP 1.3 Control Panel

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available
One Safe Source

Worldwide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S�ۢO�ۢS��� program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
World Wide Product Support

Seismic Certification

  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
Certifications

UL2200 Listed; CSA 22.2; Certification of Compliance – IBC Seismic; Dual IBC & HCAI

Certfications

Se produktet i 360°

Drag your mouse to rotate the product

Se produktet i 360°

Drag your mouse to rotate the product

Kontakt

 

Ta kontakt hvis du har spørsmål.

 

  • Call
  • Arrow

 

OSLO

Bølerveien 60
N-2020 Skedsmokorset

Pon Power:        +47 23 17 05 00
E-post:                [email protected]

Send meg et tilbud. 

250/250
Jeg ønsker å motta nyhetsbrev fra Pon.
Kontakt Tilbake Icon - Contact Sticky Cross
  • Call
  • Arrow

RING OSS

Send oss en e-post

Vi svarer deg så fort vi kan.

Hvordan foretrekker du at vi kontakter deg? *
250/250

 

ELLER FYLL UT SKJEMA HER:

 

Fyll ut skjemaet nedenfor, så kontakter jeg deg så snart som mulig.

 

Hvordan vil du at vi skal kontakte deg? *
250/250
web-monitoring-ok