Cat MX150 Microprocessor Controller

ATS MX Contacter

A003666.png

About the Cat MX150 Microprocessor Controller

 

The MX150 microprocessor is standard with the CTG product family. The MX150 microprocessor panel controls the operation and displays thes tatus of the transfer switch's position, timer sand available sources.
As an embedded digital controller, the MX series offers high reliability and ease of unattended operation across a range of applications.

Features

Features

Features and Benefits

Features and Benefits
  • Digital timer and adjustments with 1 second resolution
  • Long lasting LED indicators and an easy-to-view LCD display
  • Inputs optoisolated for high electrical immunity to transients and noise
  • Digital voltage and frequency adjustments with1% resolution
  • Voltage and frequency sensing includes:
    –Voltage imbalance detection between phases
    –Under frequency sensing on source 2
    –3 Phase under voltage sensing on source 1(S1)
    – Normal and single phase sensing onsource (S2)
    – Emergency
  • Modular pre-signal option easily integrated into the system (e.g. elevator pre-signal and motor load disconnect)
  • Universal Motor Disconnect (UMD) available for programming to pre-signal, post-signal or both
  • Line voltage transients are isolated from the control board using remote transformers
  • Simplified major components and modules for easy replacement
  • On-board diagnostics including voltage frequency, control and timing
  • Nonvolatile memory – battery backup not required during normal source outage
  • External communication available through LonWorks/ModBus network interface (RS232,RS 422, and RS 485 are also available)
  • Maintained and momentary test positions are available to the controller
  • Test mode allows manual bypass of all transfer timers when applicable
  • Automatic daylight savings adjustment available

User-Friendly Operation

User-Friendly Operation
  • LEDs for continuous monitoring of switch position, source availability, exercise time delay operation and diagnostics
  • Simplified adjustment for voltage, frequency and time delay settings
  • Close differential 3 phase under-voltage sensing of source 1, factory standard setting 90% pickup,80% dropout (adjustable); under-frequency sensing of the source 1 factory setting 95% pickup (adjustable)
  • Voltage and frequency sensing of source 2,factory standard setting 90% pickup voltage,95% pickup frequency (adjustable)
  • Test switch (fast test/load/no load) to simulate normal source failure – automatically bypassed should source 2 fail

Contact

 

Please contact us for requests or advise. 

 

  • Call
  • Arrow

Request a quotation

 

250/250
Contact Close Icon - Contact Sticky Cross
  • Call
  • Arrow

CALL US

Opening hours: 08:00 - 16:00

  • Call Pon Equipment AS
    (for buyubg Cat maskines and worktools)
  •  
  • Call21 08 41 00
  •  
  • Call Pon Power AS
    (for buying Cat enginges and power supply)
  •  
  • Call23 17 05 00
  •  
  • Call Pon Rental AS
    (for renting machines and other equipment)
  •  
  • Call21 08 43 00

Email us

We will get in contact within 24 hours.

How would you like us to contact you? *
250/250

 

Fill in the form below and I will contact you as soon as possible.

 

How would you like us to contact you? *
250/250
web-monitoring-ok